Data provided by open.toronto.ca

Building Permit

25 150495 ALT

Cancelled
403 KEELE ST
Applied Jan 6, 2025

Project Description

Alternative solution for permit 24 210400 To provide 65 mm standpipe system hose valve connection in general conformance with the 2015 national building code (NVC ) and the 2013 edition of NFPA 14 Standard for insulation of standpipe and hose system (as referenced by the NBC and the OBC) in this fully sprinklered building.The 65 mm hose connections will be provided in lieu of hose station (38 mm and 65 mm hose valves 38 mm hose and nozzle) required by the 2012 Ontario building code. The standpipe system and hose connections will be located within exit stair enclosures, and vertical service spaces (where required)

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardS0429
Builder/OwnerN/A