Building Permit
24 129592 ALT
Inspection
29 PRINCE ARTHUR AVE
Applied Jan 28, 2008
Project Description
Alternative Solution for sprinkler Protected Glazing:Based on the limiting distance 79.74% to 80.69% of the area is required to have a fire resistance rating of not less than 1 h and is proposed to be achieved through sprinkler protected glazing/window sprinklers design in accordance with OBC 3.1.8.18. and ULC/ORD C263.1. The AHJ expressed concerns about the ability of the mullion or window frame that is located between the sprinkler protected glazed assembly and the unprotected window opening to stay in place during exposure to fire. Therefore, the proposed alternative solution addresses the protection of mullions within the sprinkler protected glazing on the south exposing face of the subject building.
Permit Details
| Permit Type | AS Alternative Solution |
| Work Type | Alternative Solution |
| Structure Type | N/A |
| Revision | 00 |
| Ward | S1127 |
| Builder/Owner | N/A |