Data provided by open.toronto.ca

Building Permit

23 220711 ALT

Closed
625 SHEPPARD AVE E
Applied Jun 4, 2020
Completed Jun 5, 2020

Project Description

The purpose of this alternative solution is to address the OBC requirement to install combination smoke and fire dampers at the duct openings that are part of the air-handling system that provides make-up air for the residential public corridors as required by Sentence 3.2.6.2.(5.1). On an alternative solution basis, it is proposed to install fire dampers only at the above noted duct openings.

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardN1729
Builder/OwnerN/A