Data provided by open.toronto.ca

Building Permit

23 157603 ALT

Inspection
875 EGLINTON AVE W
Applied Jun 19, 2015

Project Description

Proposed alternative solution to protect the standpipe riser on level 2, near the electrical closet, with fire wrap (3M Fire Barrier Duct Wrap 615+) in lieu of locating it in a 1 h fire rated vertical service space. The proposed fire wrap can provide up to 2 h fire resistance rating. The standpipe riser will be protected against mechanical damage by locating the fire wrapped riser in drywall enclosure.

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardS1224
Builder/OwnerN/A