Data provided by open.toronto.ca

Building Permit

22 126194 ALT

Closed
59 MUTUAL ST
Applied Oct 17, 2022
Completed Nov 18, 2022

Project Description

The proposed IVY Development (59-71 Mutual Street) will be provided with a standpipe system. In lieu of required fire hose stations, it is proposed to install 65 mm fire hose valve connections within the exit stairs in accordance with the NBC and NFPA 14. Fire hose valve connections will be located such that sufficient fire hose coverage of 33 m (30 m hose length + 3 m hose stream) is provided in all floor areas in the building.

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardS1332
Builder/OwnerN/A