Data provided by open.toronto.ca
Building Permit
22 182369 ALT
Inspection
130 ADELAIDE ST W
Applied Apr 16, 2022
Project Description
It is proposed to address the 20 m2 opening between 24 to 25 floor levels of the building. In addition, it proposes the use of smoke baffles with closely space sprinklers and smoke detection system to address the floor opening in accordance with NFPA 13-2013, 8.15.4. around the opening along with a smoke detection system near the smoke baffles.
Permit Details
| Permit Type | AS Alternative Solution |
| Work Type | Alternative Solution |
| Structure Type | N/A |
| Revision | 00 |
| Ward | S1031 |
| Builder/Owner | N/A |