Data provided by open.toronto.ca
Building Permit
21 119479 ALT
Closed
191 CHURCH ST
Applied Oct 24, 2024
Completed Dec 11, 2024
Project Description
This application details the proposed alternative solution to protect the gas fuel line serving the emergency generator with 3M FireMaster Duct Wrap system in lieu of locating the gas fuel pipe in a fire enclosure or a service room. The proposed assembly has achieved a 2h fire resistance rating when tested in accordance with CAN/ULC S101 and ISO 6944.
Permit Details
| Permit Type | AS Alternative Solution |
| Work Type | Alternative Solution |
| Structure Type | N/A |
| Revision | 00 |
| Ward | S1332 |
| Builder/Owner | N/A |