Data provided by open.toronto.ca

Building Permit

23 131285 ALT

Closed
3070 ELLESMERE RD
Applied Aug 14, 2018
Completed Jul 21, 2020

Project Description

Proposal to omit the installation of hose cabinets within floor areas. Rather, 65 mm hose connections will be installed within the exit stair shafts as required for this Project in accordance with the 2015 National Building Code of Canada (NBC) Sentence 3.2.5.10.(1) and NFPA 14-2013, "Installation of Standpipe and Hose Systems". Additionally, 65 mm hose connections will be installed where required throughout the floor area to provide the required 30 m hose coverage to the floor areas of the Project. It should be noted that this approach to compliance with the OBC follows the informal policy of Toronto Fire Services for the omission of fire hose cabinets within floor areas.

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardE2423
Builder/OwnerN/A