Data provided by open.toronto.ca
Building Permit
19 170558 ALT
Closed
2221 YONGE ST
Applied Aug 5, 2025
Completed Aug 21, 2025
Project Description
Alterative solution to use grade TP 304 SCH 10 and 40 stainless steel (SS) pipe as alternate to type L Cooper for domestic cold water main riser for added safety of higher working pressure rating of SS pipe (listed @ 1000 PSIG) compared to Tupe L Copper (listed @ 504 PSIG). SS pipe proposed to installed using victaulic rigid coupling style 89 and 107N for joint fittings.
Permit Details
| Permit Type | AS Alternative Solution |
| Work Type | Alternative Solution |
| Structure Type | N/A |
| Revision | 00 |
| Ward | S1228 |
| Builder/Owner | N/A |