Data provided by open.toronto.ca

Building Permit

19 162909 ALT

Closed
2205 SHEPPARD AVE E
Applied Oct 16, 2019
Completed Mar 10, 2022

Project Description

Proposal to use grade TP304 SCH 10 stainless steel (SS) pipe as alternate to type L copper for domestic water main riser for added safety of higher working pressure rating of SS pipe (listed @1,000 PSIG) compared to type L copper (listed @504 PSIG). SS pipe proposed to be installed using victaulic IPS stainless steel pipe pressfit system for joint fittings. (Relates to Building Permit 16 268547)

Permit Details

Permit TypeAS Alternative Solution
Work TypeAlternative Solution
Structure TypeN/A
Revision00
WardN1731
Builder/OwnerN/A